  • A510 / A600 series inverter installed with A600ws6 control card can realize the circulation and constant pressure water supply of two pumps driven by one.The utility model can realize the common constant pressure water supply of one use, one supplement and one use, one standby, providing conve

  • 产品介绍
  • 产品参数
  • 产品选型
  • 安装尺寸
  • 资料下载

A510 / A600 series inverter installed with A600ws6 control card can realize the circulation and constant pressure water supply of two pumps driven by one. The utility model can realize the common constant pressure water supply of one use, one supplement and one use, one standby, providing convenience for customers and reducing the costs.

Code

Setting Value

Descriptions

F0.02

8

PID closed loop operation control valid

F9.04

1.00

PID gives maximum feedback range. If the maximum range of remote pressure gauge is 1 MPa, the parameter is set to 1.00, the maximum range of remote pressure gauge is 0.6MPa, and the parameter is set to 0.60.

F9.36

75.0%

Wake up coefficient (this parameter may not be set if sleep wake-up function is not required)

F9.37

Actual determination

Wake up delay time (this parameter may not be set if sleep wake-up function is not required)

F9.38

38.00Hz

Sleep frequency (this parameter may not be set if sleep wake function is not required)

F9.39

Actual determination

Sleep wake delay time. 0 is invalid for sleep (this parameter may not be set if sleep wake function is not required)

F9.42

2

Sleep wake delay 0 is not valid for sleep (this parameter may not be set if sleep wake function is not required)

F9.43

Actual determination

(Min.)

Timing rotation time. 0 is invalid for timed rotation.

Note: In the monitoring state, the set pressure can be adjusted through the up and down keys of the keyboard. If 0.20 MPa is displayed, the set 2 kg pressure will be indicated

A600-WS6 extension card (one drag two)
105.5 X 70 (mm)